Use Case:  Close Enclosure On Bad Meteo Conditions

Description This is a monitor function that checks the Meteo Conditions (Wind/Humidity/Temp dew point etc...) against given limits and accordingly closes the AT Enclosure
On Wind Speed > 18m/s, AMOS PLC handles automatically the closing of the enclosure.
This UC uses Close Enclosure

Role(s)/Actor(s)
Secondary: ASM,Axis,Enclosure

PriorityCritical.

Performance2 minutes

FrequencyAt any time.

[Design Description
  Entry]

Package Assignment Enclosure Subsystem.

Preconditions

Basic Course

Exception CourseMeteo OK

Exception CourseCommand failed

Postconditions

Issues to be Determined or Resolved

Notes: In order to avoid racing conditions, ATCS wind speed limit shall be lower than the AMOS PLC limit value (e.g. 15m/s). This would garanty that ATCS first sends the command to close the enclosure before the PLC does it. One could align on wind speed limit as of UT1.